Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
298 Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Input/holding register
Designation
Type
Range
Unit
Default
Comments
Info
Access
1)
Address
high/low
Bit
0x4190
high Motor protection -
Delay with
unbalance
Byte 0 ...
255
100
ms
5 IM UM
(+)
r/w
low Interlocking time Byte 0 ...
255
1 s 0
r/w
0x4191
high FB time Byte 0 ...
255
100
ms
5 0 = Disabled
r/w
low Trip level I> Byte 0 ...
255
4 % /
I_s
0 IM UM
(+)
r/w
0x4192
high Warning level I> Byte 0 ...
255
4 % /
I_s
0 IM UM
(+)
r/w
low Trip level I< Byte 0 ...
255
4 % /
I_s
0 IM UM
(+)
r/w
0x4193
high Warning level I< Byte 0 ...
255
4 % /
I_s
0 IM UM
(+)
r/w
low Stalled rotor level Byte 0 ...
255
4 % /
I_s
0 IM UM
(+)
r/w
0x4194
high Trip delay I> Byte 0 ...
255
100
ms
5 IM UM
(+)
r/w
low Warning delay I> Byte 0 ...
255
100
ms
5 IM UM
(+)
r/w
0x4195
high Trip delay I< Byte 0 ...
255
100
ms
5 IM UM
(+)
r/w
low Warning delay I< Byte 0 ...
255
100
ms
5 IM UM
(+)
r/w

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals