Loading...
Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
190 Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Byte.Bit
Designation (PRM group)
Type
Range
Unit
Default
Note
Information
45.0 Warning level 0/4-20 mA< Byte 0 - 255 *128 0
AM1
46.0 Trip delay P> Byte 0 - 255 100
ms
5
UM(+)
47.0 Warning delay P> Byte 0 - 255 100
ms
5
UM(+)
48.0 Trip delay P< Byte 0 - 255 100
ms
5
UM(+)
49.0 Warning delay P< Byte 0 - 255 100
ms
5
UM(+)
50.0 Trip delay cos phi< Byte 0 - 255 100
ms
5
UM(+)
51.0 Warning delay cos phi< Byte 0 - 255 100
ms
5
UM(+)
52.0 Trip delay U< Byte 0 - 255 100
ms
5
UM(+)
53.0 Warning delay U< Byte 0 - 255 100
ms
5
UM(+)
54.0 Trip delay 0/4-20 mA> Byte 0 - 255 100
ms
5
AM1
55.0 Warning delay 0/4-20 mA> Byte 0 - 255 100
ms
5
AM1
56.0 Trip delay 0/4-20 mA< Byte 0 - 255 100
ms
5
AM1
57.0 Warning delay 0/4-20 mA< Byte 0 - 255 100
ms
5
AM1
58.0 Delay limit 1 Byte 0 - 255 100
ms
5
BU2(+)
59.0 Delay limit 2 Byte 0 - 255 100
ms
5
BU2(+)
60.0 Delay limit 3 Byte 0 - 255 100
ms
5
BU2(+)
61.0 Delay limit 4 Byte 0 - 255 100
ms
5
BU2(+)
62.0
TM - Hysteresis
Byte
0 - 255
1 K
5
TM1 MM
63.0
Max. star time
Byte
0 - 255
1 s
20
Star-delta starter
BU0 BU2(+)
64.0 UVO time Byte 0 - 255 100
ms
0 BU2(+)
65.0
Staggering time
Byte
0 - 255
1 s
0
BU2(+)
66.0 Analog value recording - Sampling
rate
Byte 0 - 20 5% 0 BU2(+)
67.0 Calculation module 2 -
Denominator 1
Byte 0 - 255 0 BU2(+)
68.0
Calculation module 2 - Numerator 2
Byte
0 - 255
0
BU2(+)
69.0
Calculation module 1 - Denominator
Byte
0 - 255
0
BU2(+)
70.0 Truth table 4 type 3I/1O Byte 0 -
11111111B
0 BU0,
BU2(+)