Communication
2.2 PROFINET communication
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
79
A pause time is transferred with the "Start_Pause" command. SIMOCODE pro V PN (GP)
executes this command if the pause time is greater than the minimum pause time configured
in the device. The minimum pause time of the motor is configured with the SIMOCODE ES
software under "PROFIenergy." The minimum pause time is preset to the smallest possible
value 0.1 s. You can increase the minimum pause time if executing the command in longer
pauses is convenient for technological reasons.
The "End_Pause" command results in the stop command being canceled at the PLC/PCS
control station and the motor being switched on again via enabled control stations.
Note
Command "End_Pause"
The command to switch on has to be output again because subsequent automatic switch
-on
Note
Switching on the motor in the paused condition
If the PLC/PCS control station is disabled, the motor can also be switched on in the paused
condition.
Depending on the use of the current measuring or the current-voltage measuring module,
the following measured values are supported:
Table 2- 29 Query_Measurement
Average phase current I_L A
200 Active energy import (total) Energy W Wh