Table 5-3 Vector drive
Example Settings
Vector drive (chassis format)
Current controller cycle = 375 µs
Speed controller cycle = 1.5 ms
T
I
= T
O
= At least 375 µs
T
DP
= 1.5 ms (... or 3 ms, or 6 ms ....)
T
MAPC
= T
DP
For the SIMOTION D410, a minimum of 2 ms is recommended for
the servo cycle.
For this reason, set T
MAPC
= T
DP
= 3 ms or higher.
Vector drive (PM340)
Current controller cycle = 500 µs
Speed controller cycle = 2 ms
T
I
= T
O
= At least 500 µs
T
DP
= 2 ms (... or 4 ms, 8 ms, ....)
T
MAPC
= T
DP
Note
Vector
drives in chassis format can also be operated with a current controller sampling time
of 400 µs (among other settings).
In a SIMOTION context, the following should be considered:
●
A current controller sampling time of 400 µs is only possible if control is via a
SINAMICS S120 control unit, which is not operated isochronously via PROFIBUS/
PROFINET on SIMOTION D.
● If the bus is operated isochronously, only cycles with an integer multiple of 125 µs are
possible (instead of 400 µs, so 375 µs or 500 µs, for example).
● The PROFIBUS Integrated of a SIMOTION D410 is always isochronous. This means that
a current controller sampling time of 400 µs is not possible.
● With CU parameter p0092 = 1, the sampling times are preassigned in a way that enables
isochronous operation with a control system.
Output cams / measuring inputs with vector drives
With vector drives, the cycle clock ratios (current controller cycle clock, speed controller cycle
clock, sampling time of the inputs/outputs, etc.) depend on the number of vector drives, or with
chassis units also on the device type used.
Note the information in Section Current controller cycle clocks <> 125 µs / use of output cams
and measuring inputs (Page 107).
Additional references
Additional information on quantity structures and cycle clock settings can be found in the
SINAMICS S120
Function Manual.