6.2 Replacing modules (spare part scenario)
6.2.1 Spare parts replacement for SIMOTION D410
Use of used modules
If a used D410 is used for the module replacement, we recommend that the retained data be
deleted from the used D410.
Two options are available for this.
Table 6-1 Options for deleting the retain data
Option Reference to description Notes
Module memory reset See Section Resetting the memory of
SIMOTION D410 (Page 152
)
Control via an operating mode
switch (setting MR).
This is available on all
SIMOTION platforms
Deleting and restoring non-
volatile SIMOTION data
See Section Deleting/restoring non-
volatile SIMOTION data (Page 209
)
Control via a service switch. Is
only available on SIMOTION D.
NOTICE
Unintentional restoration of the default settings instead of memory reset
When
the operating mode switch is set to switch position S1/S2/S3 = OFF (MRES), switching
the power OFF/ON performs "Restore default settings" instead of "Memory reset."
To avoid and unintentional/accidental deletion of the project data on the CF card, we
recommend that the retain data be deleted via the service selector switch.
Maintenance and service
6.2 Replacing modules (spare part scenario)
SIMOTION D410
Commissioning Manual, 04/2014 167