E74 Maximum values of internal physical variables reached
The error occurs if the variables in the mathematical calculation model exceed the following
limits:
psi_model -4000 4000 [cgr]
psip_model -2000 · 2pi · 5 -2000 · 2pi · 5 [cgr/s]
psi_ofs_model -4000 4000 [cgr]
In this case, the calculation model has oscillated uncontrollably and all movements must be
terminated.
Procedure in the event of an error
Set the control bits "move," "move_SkA," and "AS_ON" to zero.
You can use control bit "reset_mdl" to reset the mathematical calculation model only if error
E74 occurs.
Error bit: Error word 2, bit 5
Error type: Error
Remedy: 1. Eliminate the causes:
Incorrect parameterization
Erroneous input signals
Control errors
(e.g. control bits spreader_bit0 and spreader_bit1)
2. Acknowledge the error with control bit reset_mdl
3. Check the skew drive
E75 Monitoring of the magnitude of the skew oscillation
The error is set if (|psi_modell|>P314) or (|psi_kam|>P314) applies. If the error is set, skew
damping must be deactivated via "AS_ON"=0.
The error is reset if the absolute values of the two angles stated above are below value P317
for duration P318.
Error bit: Error word 2, bit 6
Error type: Error
E76 Error in parameterization of position limits TLS
The condition in Chapter TLS inching and go to zero positions (Page 356) was not considered
in the parameterization. Therefore only a procedure with mode_comm = 1 is possible.
Error bit: -
Error type: Alarm
Alarm, error, and system messages
10.5 Error messages
SC integrated STS, GSU
390 Operating Instructions, 07/2019, A5E48271265B AA