The parameter is only operative with fixed blocked regions.
Default: 100 [mm] min: 0 [mm] max: 2000 [mm]
Access code: 1 Display: Always
P239 Commissioning status
Information encoded bit by bit indicating which commissioning steps have been completed
successfully.
Default: 0 min: 0 max: 2147483647
Access code: 3 Display: Always
11.9 TLS
P240 Activate TLS control
Activate TLS control
Default: 0 min: 0 max: 1
Access code: 0
Note
TLS parameters P241 - P336 are only displayed if TLS control is activated (P240, selection 1
= ON).
P241 Position conversion factor cylinder A
Position conversion factor
POS_CAL_A [mm] = RPOS_A · P241
Default: 1 min: -100000 [mm] max: 100000 [mm]
Access code: 0
P242 Position conversion factor cylinder B
Position conversion factor
POS_CAL_B [mm] = RPOS_B · P242
Default: 1 min: -100000 [mm] max: 100000 [mm]
Access code: 0