P332 Normalization value skew drive
Normalization value for the velocity bspeed_skewaxis_norm of the skew drive
Default: 32767 min: 1 max: 32767
Access code: 0
P333 Connection of anti-wind-up function
Connection of anti-wind-up function
0: Connection of anti-wind-up function off
1: Connection of anti-wind-up function on
This parameter can be used to activate the special function "Anti-wind-up" for the electric skew
drive.
As a general rule, the risk of unstable closed-loop control behavior increases when the skew
damping factor P300 is set to a high value. This function reduces the risk that the skew damping
closed-loop control will become unstable.
Note
Parameters P334 and P335 must be left in their default settings when the anti-wind-up function
is activated.
Changes can result in unstable closed-loop control behavior.
Default: 0 min: 0 max: 1
Access code: 0
P334 Bandwidth of anti-wind-up function
Bandwidth of anti-wind-up function
Default: 1.41 min: 1 max: 2
Access code: 3
P335 Damping of anti-wind-up function
Damping of the anti-wind-up function
Default: 0.3 min: 0.1 max: 1
Access code: 3
Parameters
11.9 TLS
SC integrated STS, GSU