10.03
4.13 Monitoring functions
4-158
Siemens AG, 2003. All rights reserved
SINUMERIK 840D/SIMODRIVE 611 digital, HLA Module (FBHLA) - 10.03 Edition
5625 PROG_SIGNAL_ON_DELAY Cross reference: -
Pickup delay of variable signaling function Related to:
HLA
Protection level:
3/3
Unit:
-
Default:
0
Minimum:
0
Maximum:
10 000
Data type:
UNS.DWORD
Active:
Immediately
Enter the pickup delay for setting the message if the monitored quantity ex-
ceeds the set threshold (with hysteresis) (see diagram under
MD 5620, Fig. 4-21).
Note
Changing the settings in MD 5625: PROG_SIGNAL_ON_DELAY and
MD 5626: PROG_SIGNAL_OFF_DELAY affects a time watchdog that is
already running. The monitor is initialized with the new time settings.
5626 PROG_SIGNAL_OFF_DELAY Cross reference: -
Dropout delay of variable signaling function Related to:
HLA
Protection level:
3/3
Unit:
-
Default:
0
Minimum:
0
Maximum:
10 000
Data type:
UNS.WORD
Active:
Immediately
Enter the dropout delay for resetting the message if the monitored quantity
drops below the set threshold (with hysteresis) (see diagram under
MD 5620, Fig. 4-21).
Note
Changing the settings in MD 5625: PROG_SIGNAL_ON_DELAY and
MD 5626: PROG_SIGNAL_OFF_DELAY affects a time watchdog that is
already running. The monitor is initialized with the new time settings.
4 Firmware Drive Functions
02.99