Functions
6-110 7SJ62 Manual
C53000-G1140-C121-1
6.10.2.2 Information List for Start Inhibit of Motors
4305 I MOTOR NOMINAL 1.0 ~ 6.0 A 5.0 A Rated Motor Current
4306 MAX.WARM STARTS 1
~ 4 2 Maximum Number of Warm Starts
4307 #COLD–#WARM 1 ~ 2 1 Number of Cold Starts – Warm Starts
4308 Kτ-FACTOR 1
~ 10 2 Kt-Factor at Stop
Addr. LCD-Text Setting Options Default
Setting
Comments
F# LCD-Text Comments
4824 66 OFF 66 Motor start protection OFF
4825 66 BLOCKED 66 Motor start protection BLOCKED
4826 66 ACTIVE 66 Motor start protection ACTIVE
4827 66 TRIP 66 Motor start protection TRIP
805 Θ Rotor Temperature of Rotor (calculated by 66)
4822 >BLOCK 66 >BLOCK Motor Startup counter