EasyManua.ls Logo

Siemens SIPROTEC 7SJ62 - Default Settings; A.8 Default Settings

Siemens SIPROTEC 7SJ62
536 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A-697SJ62 Manual
C53000-G1140-C121-1
A.8 Default Settings
Some CFC Charts are already supplied with the SIPROTEC
®
device:
Device and System
Logic
:
Figure A-16Device and System Logic
Set points Using modules on the running sequence “measured value processing”, a low current
monitor for the three phase currents is implemented. The output message is set high
as soon as one of the three phase currents falls below the set threshold:
Figure A-17 Undercurrent monitoring 37-1
IN: Device, General SP
OUT: Control Device Block Data IntSP
IN: Control Device GndSwit. DP
OUT: Device, General Feeder gnd IntSP
IN: Set points 37-1 LV
IN: Measurement Ia = MV
IN: Set points 37-1 LV
IN: Measurement Ib = MV
IN: Set points 37-1 LV
IN: Measurement Ic = MV
OUT: Set points SP. 37-1
alarm OUT
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Related product manuals