4.5 Manual Overwrite / Tagging
Manual Overwrite If the breaker/switch position is not available, the status of the switchgear can be man-
ually set to the actual present position using the HMI: 0DLQ0HQX → &RQWURO →
%UHDNHU6ZLWFK → 0DQ2YHUZULWH. The simulated breaker/switch position is
used for interlocking checks, and for automatically initiated control operations.
Set Status For convenience during commissioning or at other times, decoupling of the switchgear
and the protective device may be desired for a short period, without disconnecting the
wires. This function is activated using the HMI: 0DLQ0HQX → &RQWURO → %UHDNHU
6ZLWFK → 6HW6WDWXV.
Tagging To identify unusual operating conditions in the power system, tagging can be done.
The tagging can, for example, be entered as additional operating conditions in inter-
locking checks, which are set up with CFC. Tagging is configured in the same way as
for operating devices.
• The status of the tagging is displayed on the HMI, 0DLQ0HQX → &RQWURO → 7DJ
JLQJ → 'LVSOD\ (Figure 4-11),
or changed using
• 0DLQ0HQX → &RQWURO → 7DJJLQJ → 6HW.
Figure 4-11 Tagging Equipment from the HMI
7$**,1*
'LVSOD\²!
6HW²!
&21752/
%UHDNHU6ZLWFK²!
7DJJLQJ²!
,QWHUORFN²!
0$,10(18
$QQXQFLDWLRQ²!
0HDVXUHPHQW²!
&RQWURO²!
Note:
The Manual Overwrite function is always done using the HMI on the SIPROTEC
®
4
devices.