EasyManuals Logo
Home>Siemens>Relays>SIPROTEC 7SJ62

Siemens SIPROTEC 7SJ62 Instruction Manual

Siemens SIPROTEC 7SJ62
536 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #292 background imageLoading...
Page #292 background image
Functions
6-152 7SJ62 Manual
C53000-G1140-C121-1
Address  %$/$1&(9²/,0,7 determines the limit voltage (Phase-to-Phase),
above which the voltage symmetry monitor is effective (see also Figure 6-63). Address
 %$/)$&7259 is the associated symmetry factor; that is, the slope of the
symmetry characteristic curve (Figure 6-63).
Address  %$/$1&(,/,0,7 determines the limit current, above which the cur-
rent symmetry monitor is effective (see also Figure 6-62). Address  %$/)$&
725, is the associated symmetry factor; that is, the slope of the symmetry charac-
teristic curve (Figure 6-62).
Address  Σ,7+5(6+2/' determines the limit current, above which the current
sum monitor (see Figure 6-61) is activated (absolute portion, only relative to I
N
). The
relative portion (relative to the maximum conductor current) for activating the current
sum monitor (Figure 6-61) is set at address  Σ,)$&725.
6.17.2.1 Settings for Measured Values Monitoring
In the list below, the setting ranges and default setting values for current-based set-
tings are for a device with a nominal current rating I
N
= 5 A. For a nominal current rat-
ing I
N
= 1 A, divide the Setting Options values and Default Setting values by 5. Con-
sider the current transformer ratios when setting the device with primary values.
Note:
Current sum monitoring is only in effect if the ground current for the line to be protect-
ed is connected.
Addr. LCD-Text Setting Options Default Setting Comments
8101 MEASURE. SUPERV OFF
ON
ON Measured Value Monitor
8102 BALANCE V–LIMIT 10
~ 100 V 50 V Symmetry Uph: Threshold Value
8103 BAL. FACTOR V 0.58
~ 0.90 0.75 Symmetry Uph: Characteristic
8104 BALANCE I LIMIT 0.50 ~ 5.00 A 2.50 A Symmetry Iph: Threshold Value
8105 BAL. FACTOR I 0.10
~ 0.90 0.50 Symmetry Iph: Characteristic
8106 Σ I THRESHOLD 0.25
~ 10.00 A 0.50 A Sum I: Threshold Value
8107 Σ I FACTOR 0.00 ~ 0.95 0.10 Sum I: Characteristic
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals