Functions
6-1137SJ62 Manual
C53000-G1140-C121-1
Figure 6-49 Typical Fault Profile for Source Side Connection of the Voltage Transformer
Figure 6-50 shows a fault profile for a load side connection of the voltage transformers.
When the circuit breaker is open, the voltage disappears and the 27-1 element picks
up and times out. When the current drops below the current flow monitoring setting at
address (i.e. the current criterion is no longer met) the 27-1 element will drop out
even though the voltage remains below the pick-up setting of the 27-1 element.
Un
U< Rf
t
U(t)
AUS
Befehl
EIN
Befehl
U<
TU <
T AUSKOM
Auslösung
Anregung
Anregeschwelle
t
Anregung
U<
Anrege-
rückfall
U<
Wie d e r-
einschalten
gesperrt
Rückfallschwelle
T AUSKOM = Mindestkommandozeit