Functions
6-1137SJ62 Manual
C53000-G1140-C121-1
Figure 6-49 Typical Fault Profile for Source Side Connection of the Voltage Transformer
Figure 6-50 shows a fault profile for a load side connection of the voltage transformers.
When the circuit breaker is open, the voltage disappears and the 27-1 element picks
up and times out. When the current drops below the current flow monitoring setting at
address  (i.e. the current criterion is no longer met) the 27-1 element will drop out
even though the voltage remains below the pick-up setting of the 27-1 element.
Un
U< Rf
t
U(t)
AUS
Befehl
EIN
Befehl
U<
TU <
T AUSKOM
Auslösung
Anregung
Anregeschwelle
t
Anregung
U<
Anrege-
ckfall
U<
Wie d e r-
einschalten
gesperrt
Rückfallschwelle
T AUSKOM = Mindestkommandozeit
7PLQFRP
'HOD\
9W
38
'2
9Q
7PLQFRP 0LQLPXP&RPPDQG/LQH
'URS2XW6HWWLQJ
3LFNXS6HWWLQJ

'URS2XW
7ULSSLQJ
6LJQDO

3LFNXS
5HFORVLQJ
6LJQDO
3LFNXS
'URS2XW
5HFORVLQJ
%ORFNHG
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals