EasyManuals Logo

Siemens SIPROTEC 7SJ62 Instruction Manual

Siemens SIPROTEC 7SJ62
536 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #339 background imageLoading...
Page #339 background image
Operators Tools
7-177SJ62 Manual
C53000-G1140-C121-1
I
1
, I
2
: positive and negative sequence components of the currents, primary in A and
kA, secondary in A and in % of the device nominal current.
Va, Vb, Vc: phase-to-ground voltages, primary in kV, secondary in V and in % of
V
Nom
/3, assuming that the phase-to-ground voltages are connected.
Va-b, Vb-c, Vc-a: phase-to-phase voltages, primary in kV, secondary in V and in %
of V
Nom
.
3V
0
or Ve-n: displacement voltage, either directly measured or calculated as
3V
0
=(Va + Vb + Vc), primary in kV, secondary in V and in % of V
Nom
/3, provided
that phase-to-ground voltages are connected.
V
1
, V
2
: positive and negative sequence components of the voltages, primary in kV,
secondary in V and in % of V
Nom
/3.
S, P, Q: Apparent, Real, and Reactive power; primary in kVA or MVA or GVA, pri-
mary in kW or MW or GW, primary in kVAR or MVAR or GVAR, and in % of S
Nom
=3
V
Nom
I
Nom
. The powers are positive if the real power and reactive power flow
into the protected equipment, assuming that this direction is set as “forwards” (Ad-
dress 0201, see Section 6.1).
cos ϕ: power factor. The sign matches that of the real power.
f: frequency in Hz.
•Θ/Θ
TRIP
: thermal value ratio, calculated temperature rise in % of the trip tempera-
ture rise or limit temperature rise.
From the
Device Front
With a device ready for operation, first press the key. The 0$,10(18 appears.
Use the key to select the menu item 0HDVXUHPHQW, and switch to the list of mea-
sured values using the key. The 0($685(0(17 selection appears. See figure 7-
21.
.
Figure 7-21 Selection of Measured Values in the HMI — Example
The measured values are divided into the following groups:
1. 2SHUDWLRQSUL Operating measured values, primary.
The measured values are converted from secondary to pri-
mary according to the settings entered for the current and
voltage transformers, and the nominal device values.
2. ,1VSULPDU\ Ground fault values, primary.
The real portion, I
Nsw
, and reactive portion, I
Nsb
, of the (re-
sidual) ground connection current. The measured values
are converted from secondary to primary according to the
settings entered for the current and voltage transformers,
and the nominal device values.
MENU
Etc.
0$,10(18

$QQXQFLDWLRQ²!
!0HDVXUHPHQW²!
0($685(0(17

!2SHUDWLRQSUL
!2SHUDWLRQVHF
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals