Technical Data
10-77SJ62 Manual
C53000-G1140-C121-1
– High Voltage Test (routine test) 500 V (rms) AC
Only Isolated Communications
and Time Synchronization Interfaces
– Impulse Voltage Test (type test) 5 kV (peak): 1.2/50 µs: 0.5 Ws: 3 positive
All Circuits Except Communications and 3 negative surges in intervals of 5 s
and Time Synchronization Interfaces,
Class III
EMC Tests for Im-
munity (Type Tests)
Standards: IEC 60255–6 and –22, (Product standards)
EN 50082–2 (Generic standard)
DIN 57 435 Part 303 ANSI/IEEE C37.90.1
and C37.90.2
– High Frequency Test 2.5 kV (Peak): 1 MHz: τ = 15 ms;
IEC 60255–22–1, Class III 400 Surges per s: Test Duration 2 s
and VDE 0435 Part 303, Class III R
i
=200 Ω
– Electrostatic Discharge 8 kV contact discharge: 15 kV air-
IEC 60255–22–2 Class IV discharge, both polarities:150 pF:R
i
=330 Ω
and IEC 61000–4–2, Class IV
– Irradiation with HF Field, 10 V/m: 27 MHz to 500 MHz
non-modulated
IEC 60255–22–3 (Report) Class III
– Irradiation with HF Field, 10 V/m: 80 MHz to1000 MHz: 80 % AM:
amplitude modulated 1 kHz
IEC 61000–4–3, Class III
– Irradiation with HF Field, 10 V/m: 900 MHz: repetition frequency
Pulse Modulated 200 Hz: duty cycle of 50 %
IEC 61000–4–3/ENV 50204, Class III
– Fast Transient Disturbance Variables/ 4 kV: 5/50 ns: 5 kHz: Burst length = 15 ms;
Burst IEC 60255–22–4 and repetition rate 300 ms: both polarities:
IEc 61000-4-4, Class IV R
i
= 50 Ω: Test Duration 1 min
– High Energy Surge Voltages
(SURGE), IEC 61000–4–5
Installation Class 3
Power Supply common mode: 2 kV: 12 Ω: 9 µF
diff. mode: 1 kV: 2 Ω: 18 µF
Measuring Inputs, Binary Inputs common mode: 2 kV: 42 Ω: 0.5 µF
and Relay Outputs diff. mode: 1 kV: 42 Ω: 0.5 µF
– Line Conducted HF, amplitude modul. 10 V: 150 kHz to 80 MHz: 80 % AM: 1 kHz
IEC 61000–4–6, Class III
– Power System Frequency Magnetic 30 A/m continuous: 300 A/m for 3 s: 50 Hz
Field IEC 61000–4–8, Class IV 0.5 mT: 50 Hz
IEC 60255–6
– Oscillatory Surge Withstand Capability 2.5 to 3 kV (Peak Value): 1MHz to 1.5 MHz
ANSI/IEEE C37.90.1 damped wave: 50 surges per s:
duration 2 s: R
i
= 150 Ω to 200 Ω
– Fast Transient Surge Withstand Cap. 4 kV to 5 kV: 10/150 ns: 50 Pulse per s;
ANSI/IEEE C37.90.1 both polarities: Duration 2 s: R
i
= 80 Ω
– Radiated Electromagnetic Interference 35 V/m: 25 MHz to 1000 MHz
ANSI/IEEE C37.90.2 amplitude and pulse modulated