"NTP server 1" / "NTP server 2" boxes
●
Here, enter the key ID agreed with the provider of the NTP server.
The hash function MD5 is supported for the key.
Possible values: 0...65535
●
Here, enter the key name that helps you to identify the key with the key ID entered above.
Range of values: 5 ... 11 ASCII characters
●
If you want to use the NTP server, first select the "enable" check box.
Then enter the IP address of the NTP server in decimal numbers.
Consistency check and saving
Saving and consistency check
Once you have completed the parameter assignment in the hardware configuration, the
current version must be saved with the "Station / Save" menu. You can generate system
data blocks (SDBs) using the "Save and compile" menu later since there are still other
configuration steps necessary before the SDBs can be generated completely. When you
close hardware configuration, a dialog opens automatically prompting you to save your
entries.
When you select the "Save and compile..." function, a consistency check is run and a
message is displayed if configuration errors are detected.
Note
To be able to acquire all the c
onfigured parameters for the TD7 software following changes
in the hardware configuration of existing installations when the system data is generated, the
SINAUT configuration tool must first be started with the connection configuration and then
with the s
ubscriber administration. The project should be saved there, and the SDBs should
be generated exclusively in "Subscriber administration".
Printing module information
The information on all configured modules in the current rack or for a selected module can
be printed out using the "Station / Print..." menu.