Installation and commissioning
4.2 Mounting and connecting up a TIM
TIM DNP3
66 System Manual, 06/2014, C79000-G8976-C253-03
General notices on use in hazardous areas
Personal injury and property damage can occur.
By installing expansions that are not approved for SINAUT products or their target systems,
the requirements and regulations relating to safety and electromagnetic compatibility may
be violated.
Use only expansions approved for the system.
Risk of explosion when connecting or disconnecting the device
EXPLOSION HAZARD
DO NOT CONNECT OR DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR
COMBUSTIBLE ATMOSPHERE IS PRESENT.
EXPLOSION HAZARD
SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION
2 OR ZONE 2.
General notices on use in hazardous areas according to ATEX
Requirements for the cabinet/enclosure
When used in hazardous environments corresponding to Class I, Division 2 or Class I,
Zone 2, the device must be installed in a cabinet or a suitable enclosure.
To comply with EU Directive 94/9 (ATEX95), this enclosure must meet the requirements of
at least IP54 in compliance with EN 60529.
Suitable cables for temperatures in excess of 70 °C
If the cable or conduit entry point exceeds 70 °C or the branching point of conductors
exceeds 80 °C, special precautions must be taken. If the equipment is operated in an air
ambient between 50 °C and 70°C, only use cables with admitted maximum operating
temperature of at least 80 °C.