EasyManua.ls Logo

Siemens TIM 4R-IE DNP3 - The Modbusread Object

Siemens TIM 4R-IE DNP3
354 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
System Manual, 06/2014, C79000-G8976-C253-03
229
Data type:
By spe
cifying the data type, you specify the data type with which the data is
transferred from the S7 CPU to the MODBUS slaves. The drop
-down list
offers the following data types for the three memory areas:
BOOL, BYTE, CHAR, WORD, DWORD, INT, DINT, REAL
Number:
Number of double words included in the array (maximum 100).
DB No.:
Specifies the DB number in the CPU if the data block memory area (DB) was
selected
Address [Byte]:
Input field for the byte number in the selected memory area. For data types
involving
more than one byte (WORD, DWORD), the least significant byte
number must be entered as in STEP 7.
MODBUS output
Here, the register address on the MODBUS slave to which the data will be written is
specified.
Name:
MODBUS output
Register
address:
Specifies the register address.
You will find the permitted address ranges in the documentation of your MODBUS
slave.
Range of
values:
0...65535
Function code: Specifies the MODBUS data type. The following MODBUS data types are available:
Write single coil
(write 1 value, 1 bit)
Write multiple coils
(write multiple values,1 bit)
Write single register
(write 1 parameter,16 bits)
Write multiple registers
(write multiple parameters,16 bits)
Default setting:
MODBUS output
Function code: Write single register
S7 CPU input address
Data type: WORD
Number: 1

Table of Contents

Related product manuals