Installation and commissioning
4.2 Mounting and connecting up a TIM
TIM DNP3
System Manual, 06/2014, C79000-G8976-C253-03
67
Protection against transient voltage surges
Provisions shall be made to prevent the rated voltage from being exceeded by transient
voltage surges of more than 40%. This criterion is fulfilled, if supplies are derived from
SELV (Safety Extra-Low Voltage) only.
General notices on use in hazardous areas according to UL HazLoc / FM
Do not disconnect while circuit is live when a flammable or combustible atmosphere is
present.
Substitution of components may impair suitability for Class I, Division 2.
Personal injury and property damage can occur.
In hazardous areas, personal injury or property damage can result if you create or break an
electrical circuit during operation of a SINAUT product (for example, by means of plug-in
connections, fuses, switches).
Do not create or break live electric circuits unless you are certain there is no danger of
explosion.
If you use SINAUT products under FM conditions, they must be mounted in an enclosure
that at least corresponds to IP54 in accordance with EN 60529.
Note
This equipment is suitable for use in Class I, Division 2, Group A, B, C, D or non
-hazardous
Note
This equipment must be set up according to the NEC (National E
lectrical Code) stipulations.
When used in environments according to class I, division 2 (see above) , the SINAUT
products must be installed in an enclosure that corresponds to at least IP54 according to EN
60529.