The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
System Manual, 06/2014, C79000-G8976-C253-03
177
Parameters in the TD7 Message receive box
Name:
Check of source address
Range of
values:
Function active, function deactivated
Default:
Function active
Explanation:
With this parameter, you specify whether or not the source address of the
sending subscriber
is checked prior to accepting data from a received
message. If the function is activated, all messages that do not originate from
the configured partner are discarded.
Note
: If a data object receives messages from several partners, the check of
the source address must be deactivated.
Parameters in the MODBUS polling cycle box
The parameters in this box are relevant only if the TIM uses MODBUS communication.
Name:
S7 CPU polling pause
Range of
values:
0 to 65535 [ms]
Default:
200
Explanation:
The parame
ter specifies the duration of the pause on the TIM between two
CPU polls.
Name:
MODBUS polling pause
Range of
values:
0 to 65535 [ms]
Default:
200
Explanation:
The parameter specifies the duration of the pause on the TIM between two
MODBUS slave polls.
Copying basic settings to other TIMs
Once the basic settings of a subscriber with TD7onTIM have been made, the settings can
also be transferred to other TIMs that require the same parameters. Follow the steps
outlined below:
1. Select a TIM for which you have already set the parameters in the subscriber list.
2. Select "Copy" in the shortcut menu (right mouse button).
3. Select a second TIM.
4. Transfer the parameters to this second TIM using "Paste" in the shortcut menu.