The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
164 System Manual, 12/2015, C79000-G8976-C253-04
Object
group
Variation
Format according
to the DNP3 speci-
fication
Station type
TD7onTIM object
S7 data
type
DNP3 level of the part-
ner ***
23
*
2 Frozen counter
event - 16-bit with
flag
Station Cnt01D_S WORD
30 1 Analog input -
32-bit with flag
Station Dat12D_S DINT
Master sta-
tion
Dat12D_R
2 Analog input -
16-bit with flag
Station Ana04W_S,
Mean04W_S
WORD
Dat12D_S BYTE, INT,
WORD
Master sta-
tion
Ana04W_R,
Mean04W_R
WORD
Dat12D_R BYTE, INT,
WORD
5 Analog input -
32-bit float with
flag
Station
Dat12D_S
REAL DNP3 level 5 only
Master sta-
tion
Dat12D_R
32 1 Analog input event
- 32-bit
Station
Dat12D_S
DINT DNP3 level 1 to 3
Master sta-
tion
Dat12D_R
2 Analog input event
- 16-bit
Station
Ana04W_S
WORD
DNP3 level 1 to 3
Mean04W_S
WORD
Dat12D_S BYTE, INT,
WORD
Master sta-
tion
Ana04W_R WORD
Mean04W_R
WORD
Dat12D_R BYTE, INT,
WORD
3 Analog input event
- 32-bit with time
Station
Dat12D_S
DINT As of DNP3 level 4
Master sta-
tion
Dat12D_R
4 Analog input event
- 16-bit with time
Station
Ana04W_S
WORD
As of DNP3 level 4
Mean04W_S
WORD
Dat12D_S BYTE, INT,
WORD
Master sta-
tion
Ana04W_R
WORD
Mean04W_R
WORD
Dat12D_R BYTE, INT,
WORD
7 Analog input event
- 32-bit float with
time
Station
Dat12D_S
REAL DNP3 level 5 only
Master sta-
tion
Dat12D_R

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens TIM 4R-IE DNP3 and is the answer not in the manual?

Siemens TIM 4R-IE DNP3 Specifications

General IconGeneral
BrandSiemens
ModelTIM 4R-IE DNP3
CategoryControl Unit
LanguageEnglish

Related product manuals