The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
System Manual, 06/2014, C79000-G8976-C253-03
167
Object
group
Variation
Format according
to the DNP3
specification
Station type
TD7onTIM object
S7 data
type
DNP3 level of the
partner ***
22 2 Counter event -
16-bit with flag
Station
Cnt01D_S, Cnt04D_S
WORD DNP3 level 1 to 4
Master
station
Cnt01D_R, Cnt04D_R
6 Counter event -
16-bit with flag and
time
Station
Cnt01D_S, Cnt04D_S
WORD DNP3 level 5 only
Master
station
Cnt01D_R, Cnt04D_R
23
*
2 Frozen counter
event - 16-bit with
flag
Station Cnt01D_S WORD
30 1 Analog input -
32-bit with flag
Station
Dat12D_S
DINT
Master
station
Dat12D_R
2 Analog input -
16-bit with flag
Station Ana04W_S,
Mean04W_S
WORD
Dat12D_S BYTE, INT,
WORD
Master
station
Ana04W_R,
Mean04W_R
WORD
Dat12D_R BYTE, INT,
WORD
5 Analog input -
32-bit float with
flag
Station
Dat12D_S
REAL DNP3 level 5 only
Master
station
Dat12D_R
32 1 Analog input event
- 32-bit
Station
Dat12D_S
DINT DNP3 level 1 to 3
Master
station
Dat12D_R
2 Analog input event
- 16-bit
Station
Ana04W_S
WORD
DNP3 level 1 to 3
Mean04W_S
WORD
Dat12D_S BYTE, INT,
WORD
Master
station
Ana04W_R
WORD
Mean04W_R
WORD
Dat12D_R BYTE, INT,
WORD
3 Analog input event
- 32-bit with time
Station
Dat12D_S
DINT As of DNP3 level 4
Master
station
Dat12D_R
4 Analog input event
- 16-bit with time
Station Ana04W_S WORD As of DNP3 level 4
Mean04W_S
WORD
Dat12D_S BYTE, INT,
WORD
Master
station
Ana04W_R
WORD
Mean04W_R
WORD
Dat12D_R BYTE, INT,
WORD