The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
184 System Manual, 06/2014, C79000-G8976-C253-03
Data object
Object type and function
Number of
indexes
occupied
DNP3 object group
[variation]
(S7 data type)
DNP3 level *
Use in stations
type **
Par12D_S
Parameter object for send
direction
Send max. 12 double words
with parameters or setpoints,
object with 3 channels:
"LocalOperation"
- not used -
"ReturnedParameter"
Function: Returned
parameter
Channel type: Data receive
1 ... 12
40 [1] (DINT)
***
42 [3] (DINT)
***
1 ... 5
4 ... 5
M
"ParameterInput"
Function: Parameter input
Channel type: Setpoint
send
1 ... 12
41 [1] (DINT)
****
1 ... 5
Par12D_R
Parameter object for receive
direction
Receive max. 12 double words
with parameters or setpoints,
object with 3 channels:
"Local"
- not used -
"LocalParameterInput"
Function: Local parameters
Channel type: Data send
1 ... 12
40 [1] (DINT)
***
42 [3] (DINT)
***
1 ... 5
4 ... 5
S
"ParameterOutput"
Function: Parameter output
Channel type: Setpoint
receive
1 ... 12
41 [1] (DINT) 1 ... 5
Universal data objects
Dat12D_S
Data object for send direction
Send max. 12 double words (at
least 1 double word) with any
information
1 ... 12
30 [1] (DINT)
30 [5] (REAL)
32 [1] (DINT)
32 [3] (DINT)
32 [7] (REAL)
41 [1] (DINT)
41 [3] (REAL)
1 ... 5
5
1 ... 3
4 ... 5
5
1 ... 5
5
S
S
S
S
S
M
M
2 ... 24
30 [2] (INT, WORD)
32 [2] (INT, WORD)
32 [4] (INT, WORD)
41 [2] (INT, WORD)
1 ... 5
1 ... 3
4 ... 5
1 ... 5
S
S
S
M