The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
System Manual, 06/2014, C79000-G8976-C253-03
221
This is the time during which the command output of the channel is active.
When the configured time has elapsed, the bit is reset to zero by TD7onTIM.
Set01W_S sends 1 setpoint. The locally valid setpoint can also be indicated by this object.
The object can only be used in the master station.
Checking the input time and 1-out-of-n check of entries
For information on checking the input time and on the 1-out-of-n check of inputs for
increased reliability when inputting setpoints and parameters, see the description of
"Par12D_S" below.
Channel type: Data receive Function: Status 'Local setpoint input'.
The channel is not used for the DNP3 protocol.
Channel "ReturnedSetpoint"
Channel type: Data receive
Function: Mirrored back setpoint
The partner object in the station that receives the setpoint mirrors back the currently valid
setpoint if the "LocalSetpointInput" channel parameter is set (see Set01W_R). This mirrored
back value is displayed here at the ReturnedSetpoint output.
If you do not require the parameter, leave it disabled.
Channel type: Setpoint send
Function: Setpoint input
The entered setpoint is sent to the partner object via this channel. This channel of the object
corresponds to the DNP3 object group 41 with the "Direct Operate" function code.
Set01W_R receives 1 setpoint. The object also has an input over which the locally valid
setpoint can be returned.
The object can only be used in the station.
Channel type: Data send Function: Status input mode 'local'.
The channel is not used for the DNP3 protocol.