The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
224 System Manual, 12/2015, C79000-G8976-C253-04
If the serial interface is set to the standard RS-485, up to 8 MODBUS slaves can be
connected and monitored (1 slave with RS-232).
Internal partner number of TD7onTIM, cannot be set.
Note on the gateway number
In the subscriber management, if a TIM is selected with TD7onTIM with the
system object “ModbusGateway“, in the object list in the column “Partner
no.” with
the Modbus objects, the gateway number is displayed preceded by
S7 CPU status output byte
The following options are available:
DB: Data block
Memory bit: Memory bit area
Output: Process output image (PIQ)
Specifies the DB number in the CPU if the data block memory area (DB) was
selected
Input box for the byte number in the selected memory area
In the 8 input boxes, the MODBUS slaves to be monitored are assigned to
the
8 status bits of the output byte. The MODBUS address is specified for
Status = 0: Problem on partner or bit not assigned
The "ModbusGateway" system object is used to activate the MODBUS protocol for a serial
interface of the TIM and to configure the connection to the MODBUS slaves.
Connection to TIM interface
Specifying the serial interface of the TIM
4R-IE DNP3:
WAN 1 = interface X1
WAN 2 = interface X2