Parameter* Description
V3 Setpoint V3 setpoint alarm
Freq Setpoint Frequency setpoint alarm
Sag/Swell 1 Voltage sag/swell alarm
Current Sag Ph1** Current sag alarms for phase 1
Current Sag Ph2** Current sag alarms for phase 2
Current Sag Ph3** Current sag alarms for phase 3
4-30 Volt Intrp Ph1
4-30 voltage interruption power quality alarm for phase
1
4-30 Volt Intrp Ph2
4-30 voltage interruption power quality alarm for phase
2
4-30 Volt Intrp Ph3
4-30 voltage interruption power quality alarm for phase
3
Current Swell Ph1** Current swell alarms for phase 1
Current Swell Ph2** Current swell alarms for phase 2
Current Swell Ph3** Current swell alarms for phase 3
* Any Setpoint or Relative Setpoint module with an event priority greater than or equal to the Low
alarm event priority is also displayed on this screen.
** Enabling or disabling one phase for each alarm type will enable or disable all phases for that
type.
NOTE: Configuring alarms must be done using ION Setup.
Alarms with a priority less than Low (Info Only or None) are not displayed.
You must configure all the parameters related to the alarm for alarm functions to operate. For
example, for the Over Ia alarm to operate, you must enter the nominal value and the conditions
that define an alarm state, even if the alarm is shown as Enabled on the Alarm Setup screen.
Disabling and enabling alarms using the display
Disable alarms using the display when you are performing maintenance tasks on your system and
want to prevent nuisance alarms.
NOTE: To stop an alarm from being displayed without impacting other metering features, set the
alarm priority to Info Only.
To disable alarms using the display:
1. Press the Home button on the display.
2. Press Setup Menu > Alarm Setup.
3. Press Select.
4. Press Edit. Enter your meter’s password, if prompted.