13-2
4007ES Panel Programmer Manual (579-1167)
Adding or Editing Network Information, Continued
General Network
Programming
Guidelines
Do not make an NDU point Public above offset 1535. This only applies to the 4100+.
Never set the value of an External Analog Pseudo Point through the Network.
Do not use P210, P211 or P212 at the same time for Network System Reset.
Use P217 for Network Signal Silence.
Avoid Version Mismatch. If you change a label or device type or point type on a point that is
EXTERNAL to other nodes, you must build and download all nodes that have an external
copy of the point. If you change the Job Title in the General Info screen, or the Network
Prefix in the Network Points in the Info Screen, you must build all nodes and download all
nodes.
4007ES
Programmer
Network tab
The Network Tab provides access to the dialogs used to add and edit the lists of public and
external points. Click on the Network Tab to see the screen shown in Figure 13-1.
Figure 13-1. Network Tab