7-11
4007ES Panel Programmer Manual (579-1167)
Point Editing for TrueAlert Device, Continued
TrueAlert ES AV-L
Appliance Point
Editing
Use this device type to edit TrueAlert ES Audible/Visual LED Strobe (AV-L) appliances. The
following editing options are available for this appliance:
Table 7-8.TrueAlert ES AV-L Point Editing Options
Option Description
Custom Label This field is used to describe the appliance's function, location, or other descriptive
information.
Alternate Label This field is used to enter an alternative description of the appliance.
Style Select the Style that corresponds to the appliance or device you are programming.
• Indoor.
• Weatherproof UL/
ULC
Available candela
options:
System Default. Selecting this option sets the candela value
to the one selected in the System Option tab.
15 candela
30 candela
75 candela
Hardware. Selecting this option sets the appliance to the
setting indicated on the appliance's configuration switch or
jumper.
Operation Select the type of operation the appliance will signal.
General Evac. The strobe is automatically associated with the “ALL VISUAL”
VNAC by default. The “alarm/alert” switch on the device must
be set to "Alarm".
Other When this mode is selected the user is confirming that the
strobe does not have a default assignation to a particular
VNAC and that the VNAC must be specified by the user.
Mounting Only a wall-mounted appliance is allowed.
Candela Select the candela output of the appliance. The selection varies according to the
appliance style.
Horn Type Broadband
Tone BROADBAND
Continued on next page.

Table of Contents

Other manuals for Simplex 4007ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4007ES and is the answer not in the manual?

Simplex 4007ES Specifications

General IconGeneral
Model4007ES
CategoryFire Alarms
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
Display4.3-inch color touchscreen
Power Supply120/240 VAC, 50/60 Hz
Network ConnectivityEthernet, RS-232, RS-485
Addressable Points250
Communication ProtocolsMAPNET II
Notification Appliance Circuits4 NACs
Total Points250
AnnunciationYes
Max Devices250
Max Notification Circuits4