A-8
4007ES Panel Programmer Manual (579-1167)
Releasing Specific Controls and Indications, Continued
Pre-Discharge
LED
Programming
(Red LED)
3. Write an equation to turn off the LED when the zone releases.
4. Write (or add to an existing equation) the equation to turn off the digital pseudo during
system startup or upon system reset.
5. Choose an available RED LED on the LED Module (under the Hardware tab in the
programmer) and set its mode as "ON" and set the reference address to the list that was
assigned.