8-10
4007ES Panel Programmer Manual (579-1167)
Viewing, Adding, and Editing Lists, Continued
Elevator Recall
List
Editing Group Descriptions
Each Elevator Recall group includes a description property that allows you to change the label
of the group. To edit the group's description:
1. Click on the Elevator Recall tab at the bottom of the List Window. Double click on the
appropriate Elevator Recall list.
2. Edit the description field and click on the Apply button. Click OK to close the screen.
Zone Lists The Zone List tab provides a way to group alarm conditions into zones (up to 512 zones).
When grouped into zones, when an alarm occurs, a list of affected zones is displayed on the
panel's touchscreen. It is then possible to touch the zone in alarm to display all the points that
are in alarm in that particular zone.
To create a Zone List:
1. Open the Zone List tab in the programmer.
2. Double click on an empty Zone List. The Zone List Properties window opens.
3. Enter a custom label to describe the Zone List.
4. Enter an alternate custom label to describe the Zone List.
5. Click on the Select Point button; the Tag List window opens.
6. Select the points that you want to include in the list.
7. Click on OK to confirm the selection.