9-21
4007ES Panel Programmer Manual (579-1167)
Custom Control, Continued
Suppression
Release Device
and Point Types
Table 9-2. Valid Device and Point Types, continued
Point Type Description Valid Device Types AutoGenerates to Following Lists:
SUPDET Suppression Agent
Monitor Zone
MONA, MONB, SMONA, SMONB,
SCAN50, 4002MA, 4002MB, IAM,
SECIAM, MAZAM, MBZAM, ADRDET,
GENIAM, NULLMON,500PSM,
APM500, CM520, DM520, DMC520,
IHN135, IHN200, 500CMB, 500CMC,
500CMAB, 500CMAC, 500CMAD,
500CMAE, TFXCDM, 501CMB,
LPBD520, MD501, MD501EX, MD901,
MDR901,MDS901, MF401,
MF501,MF501HA, MF501EX, MF901,
MF901HA, MFR901HA,
MFS901HA,MER901, MFS901,
MR501, MR501EX, MR501T,
MR501TEX, MR901, MRR901,
MRS901, MS502EX, MU901, MU912,
S251, S252PLUS, All PHOTO Device
types, All ION Device types, all HEAT
Device types
L18 - General Fire Alarm Monitor Zones
L30 - Alarm Verification Group 0
L61 - Coding Group 1 - Monitor Zones
L139- Local Mode Operation Points
SUPDUMP Suppression Agent
Manual Dump
MONA, MONB, SMONA, SMONB,
SCAN50, 4002MA, 4002MB, IAM,
SECIAM, MAZAM, MBZAM, ADRPUL,
CANPUL
L18 - General Fire Alarm Monitor Zones
L30 - Alarm Verification Group 0
L61 - Coding Group 1 - Monitor Zones
L139- Local Mode Operation Points
SUPABRT Suppression Agent
Abort Zone
MONA, MONB, SMONA, SMONB,
SCAN50, 4002MA, 4002MB, IAM,
SECIAM, MAZAM, MBZAM
SUPPRES Suppression Agent
Pressure Mon
MONA, MONB, SMONA, SMONB,
SCAN50, 4002MA, 4002MB, IAM,
SECIAM, MAZAM, MBZAM
L18 - General Fire Alarm Monitor Zones
L30 - Alarm Verification Group 0
L61 - Coding Group 1 - Monitor Zones
L139- Local Mode Operation Points