7-8
4007ES Panel Programmer Manual (579-1167)
Point Editing for TrueAlert Device, Continued
TrueAlert ES AV
Appliance Point
Editing
Table 7-6. TrueAlert ES AV Point Editing Options, Continued
Option Description
Operation Select the type of operation the appliance will signal.
General Evac. The strobe is automatically associated with the “ALL VISUAL”
VNAC by default. The “alarm/alert” switch on the device must
be set to "Alarm".
Other When this mode is selected the user is confirming that the
strobe does not have a default assignation to a particular
VNAC and that the VNAC must be specified by the user.
Candela Select the candela output of the appliance. The selection varies according to the
appliance style.
Horn Type
Broadband
Multitone
Tone BROADBAND BROADBAND, 520 HZ, BELL, SLOW WHOOP, SIREN,
HILO, CHIME, HARDWARE
Coding Type Select the Coding Type to set the cadence of the audible signal.
System Default This sets the coding to the value determined in the System
Option tab.
Tem po ral
A three-pulse coding pattern consisting of three ½ second
pulses, each separated by a ½ second silence. Each three
pulse group is separated by 1 ½ seconds of silence. Pattern
repeats until alarm silence.
March 20
A coded signal that uses 20 beats per minute. Each beat
consists of 1 ½ second pulse on, 1 ½ second off. Pattern
repeats until alarm silence.
March 60
A coded signal that uses 60 beats per minute. Each beat
consists of ½ second pulse on, ½ second off. Pattern repeats
until alarm silence.
March 120
A coded signal that uses 120 beats per minute. Each beat
consists of ¼ second pulse on, ¼ second off. Pattern repeats
until alarm silence.
On Steady
On steadily.
Tem p o ra l 4
A CO gas warning that is a repeated sequence of four cycles
of 100 msec on with 100 msec off, followed by 5 seconds off.
Volume Set the appliance volume:
High
To use this option the appliance's configuration control must
be set to Panel.
Low
To use this option the appliance's configuration control must
be set to Panel.
Hardware
Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
Note: The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.