7-18
4007ES Panel Programmer Manual (579-1167)
Point Editing for TrueAlert Device, Continued
TrueAlert A/V
Appliances Point
Editing
Use this device type to edit TrueAlert Strobe Audible/Visual (A/V) appliances. The following
editing options are available for this appliance:
Table 7-15. TrueAlert AV Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Style Select the Style that corresponds to the appliance or device you are programming.
Indoor.
Available candela
options:
System Default. Sets the candela value to the one selected in
the System Option tab.
15 candela
30 candela
75 candela
110 candela
Hardware. Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
Operation The strobe and horn appliances is automatically associated respectively with the “ALL
VISUAL” and "ALL AUDIBLE" VNAC by default.
Candela Select the candela output of the appliance.
Coding Type Select the Coding Type to set the cadence of the audible signal.
System Default This sets the coding to the value determined in the System
Option tab.
Temporal A three-pulse coding pattern consisting of three ½ second
pulses, each separated by a ½ second silence. Each three
pulse group is separated by 1 ½ seconds of silence. Pattern
repeats until alarm silence.
March 60 A coded signal that uses 60 beats per minute. Each beat
consists of ½ second pulse on, ½ second off. Pattern repeats
until alarm silence.
March 120 A coded signal that uses 120 beats per minute. Each beat
consists of ¼ second pulse on, ¼ second off. Pattern repeats
until alarm silence.
On Steady On steadily.
Volume Set the appliance volume:
High To use this option the appliance's configuration control must be
set to Panel.
Low To use this option the appliance's configuration control must be
set to Panel.
Note: The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.