System Manual 5. Installation
76.7300FP11/2, Rev A 8/09 Page 2-83
System response:
------------------------------------------------------
Environmental Alarm : env1
Severity : minor
Type : MISC
Polarity : high
Message : "Miscellaneous"
State : notReady
ExtAlmEnvInput Trap : ENABLED
------------------------------------------------------
Environmental Alarm : env2
Severity : minor
Type : MISC
Polarity : high
Message : "Miscellaneous"
State : notReady
ExtAlmEnvInput Trap : ENABLED
------------------------------------------------------
Environmental Alarm : env3
Severity : minor
Type : MISC
Polarity : high
Message : "Miscellaneous"
State : notReady
ExtAlmEnvInput Trap : ENABLED
------------------------------------------------------
Environmental Alarm : env4
Severity : minor
Type : MISC
Polarity : high
Message : "Miscellaneous"
State : notReady
ExtAlmEnvInput Trap : ENABLED
__ 2. To set alarm contact 1 for open door with the normally open contacts
enter the following command:
t7300-Tellabs(config)# extern alarm env1 polarity high severity
major type opendr message open_door_alarm
Activate SNMP Traps for ENV Alarms
__ 1. To activate SNMP (Active by default) traps for ENV alarms enter the
following commands:
t7300-Tellabs# configure terminal
t7300-Tellabs(config)# extern event snmp trap env1