E6582062
11. Table of parameters 11-60
1
9
11
48 49 SCLC
Communication priority
cancel
ON: Run at the setting of <CMOd: Run command select>
and <FMOd: Frequency command select 1>
OFF: Run by communication
[6. 38. 2]
[7. 2. 1]
50 51 HD
3-wire operation hold/
stop
ON: Forward run (F), Reverse run (R) held, 3-wire operation
OFF: Deceleration stop
[7. 2. 1]
52 53 IDC
PID differential/integral
reset
ON: PID differential/integral cleared
[5. 3. 8]
[7. 2. 1]
54 55 PIDSW PID plus/minus switching
ON: Plus/minus characteristics of <F359: PID control 1>
setting
OFF: Characteristics of <F359: PID control 1> setting
[7. 2. 1]
56 57 FORCE Forced run
ON: Forced run, continues in a slight failure condition (Set
<F650: Forced run> = "1: Enabled". Frequency command
value = <F294: Preset speed 15 / Forced run speed>.)
*Stop with power off
[6. 12. 2]
[6. 31]
[7. 2. 1]
58 59 FIRE Fire speed run
ON: Fire speed run (Set <F650: Fire speed run> = "1:
Enabled". Frequency command value = <F294: Preset speed
15 / Forced run speed>.)
*Stop with power off
60 61 DWELL Dwell operation
ON: Dwell operation (Stop acceleration and deceleration and
run the motor at a constant speed)
[6. 19]
[7. 2. 1]
62 63 KEB Synchronized Acc/Dec ON: Deceleration stop with synchronizing at power failure
[7. 2. 1]
64 65 MYF My function start
ON: My function start (When <A977: My function> = "1:
Enabled by permission signal")
66 67 AUTT Offline auto-tuning
<F400> = "3" ON: Offline auto-tuning executed
<F400> = "6" ON: Offline auto-tuning executed at run
command while this signal is ON.
<F400> = "7" ON: Offline auto-tuning executed only for
<F402> at run command while this signal is ON.
[6. 23. 1]
[6. 23. 2]
[7. 2. 1]
68 69 SGSW
Speed control gain
switching
ON: Use F463-F465
OFF: Use F460-F462
[7. 2. 1]
70 71 SRVL Servo lock ON: Servo lock
72 73 SIMP Simple positioning ON: Simple positioning operation
74 75 CKWH
Cumulative power
monitor clear
ON: Clear cumulative power (kWh) monitor display
[6. 36]
[7. 2. 1]
76 77 TRACE Trace trigger ON: Trace trigger (start) signal
[7. 2. 1]
78 79 HSLL
Light-load high-speed
operation inhibited
ON: Light-load high-speed operation inhibited
OFF: Light-load high-speed operation permitted
80 81 HDFP Terminal FP output hold ON: Terminal [FP] is held ON once turned ON
82 83 HDR1 Terminal R1 output hold ON: Terminal [R1] is held ON once turned ON
84 85 HDR2 Terminal R2 output hold ON: Terminal [R2] is held ON once turned ON
88 89 UP Terminal Up frequency ON: Frequency command increased
[6. 6. 5]
[7. 2. 1]
90 91 DOWN Terminal Down frequency ON: Frequency command decreased
92 93 CLR
Terminal Up, Down
frequency clear
OFF-> ON: Clear Terminal Up, Down frequency command
94 95 DANC Dancer correction OFF ON: Dancer correction OFF [7. 2. 1]
96 97 FRR Coast stop ON: Coast stop (gate OFF)
[6. 34. 8]
[7. 2. 1]
98 99 FR Fwd/Rev ON: Forward command, OFF: Reverse command
[7. 2. 1]
100 101 RS Run/Stop ON: Run command, OFF: Stop command
Function number
Symbol Function Action
Reference
Positive
logic
Negative
logic