EasyManua.ls Logo

turck TBPN-L1-FDIO1-2IOL - Diagnostics;Status; LED Displays Channel Leds (C4 to C5)

turck TBPN-L1-FDIO1-2IOL
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
V01.0| 2017/04

TBPN-L1-FDIO1-2IOL - Standard IO-Link
3.9 Diagnostics/status
3.9.1 LED displays Channel LEDs (C4 to C5)
LED LED
GREEN
LED
RED
Meaning Remedy
IO-Link
C6, LED 12
and
C7, LED 14
Channel in IO-Link-mode
off off No IO-Link communication, diag-
nostics deactivated
connect an IO-Link device
Parameterize the channel as
DI if necessary.
wire break in IO-Link cable
possible
blink-
ing
off IO-Link communication active,
valid process data
off blink-
ing
IO-Link communication active and
module error, invalid process data
No input data received from
the connected device (only
valid for devices with an input
data length > 0),
No reaction from the con-
nected device to the sending
of output data (only valid for
devices with an output data
length > 0),
connected device sends an
error: "process data invalid".
see also:
Start-up problems – fre-
quently failure causes
(page 50)
off on No IO-Link communication
and/or module error,
invalid process data
Channel in DI-mode
off off Input active
on off Input signal active
DXP
C6, LED 13
and
C7, LED 15
off off -
on off In-/ output signal active
off on Short circuit at output of the
respective channel

Table of Contents