TBPN-L1-FDIO1-2IOL- Safe I/O channels
3.6.5 Derating curves
3.7 Safe I/O channels
The device provides two 2-channel safe digital inputs (FDI) and two safe connectors (FDX), configu-
rable as in- or outputs.
The two configurable FDX-channels can be used as input (FDI) or as output (FDO).
The safe I/O channels are designed for applications up to:
Cat4/PLe according to EN ISO 13849-1
SIL3 according to IEC 61508
SILCL 3 according to IEC62061
3.7.1 Safe status
In the safe state the device outputs are in LOW-state (0).
The inputs report a LOW-state (0) to the logic.
3.7.2 Fatal Error
The following errors lead to Fatal Error and thus to the safe state:
Incorrect wiring at the output (e.g. capacitive load, energetic recovery)
Incorrect power supply
Strong EMC disturbances
Internal device error
Max. output current, DC load Max. total current for device
Fig. 7: Derating curves