17
V01.00| 2017/04
TBPN-L1-FDIO1-2IOL- Safe I/O channels
3.4.3 I/O channels
Safety-related inputs (FDI) – C0 and C1
1 VAUX1/T1 Sensor supply/ test pulse 1
2 FDI (T2) Digital input 1
3GND (V1) Ground V1
4 FDI (T1) Digital input 2
5 T2 Test pulse 2
FE Connected to the thread of the M12 connector
Safety-related in-/outputs (FDX) – C2 and C3
1 VAUX1/T1 Sensor supply/ test pulse 1
2 FDO-/FDI (T2) Digital output/ digital input 1 (M)
3GND
V1
Ground V1
4 FDO+/FDI (T1) Digital output/ digital input 2 (P)
5 T2 Test pulse 2
6 FE Connected to the thread of the M12 connector
Universal standard I/Os – C4 and C5
1 FSO 0 Sensor supply (internal safe shutdown possible)
see
Block diagram (page 15)
2 DI/DO digital in-/output
3GND (V1) Ground V1
4 DI/DO digital in-/output
5FE Functional earth
IO-Link port 1 – C6
1 VAUX1 Class B supply
2 DI/DO digital in-/output
3GND (V1) Ground V1
4C/Q IO-Link
5 GND (V1) Functional earth
IO-Link port 2 – C7
1 FSO 1 Class B supply (internal safe shutdown possible)
see
Block diagram (page 15)
2 DI/DO digital in-/output
3GND (V1) Ground V1
4C/Q IO-Link
5 GND (V1) Functional earth
4
1
3
2
5
v
4
1
3
2
5
v