4.2 Parameter "data storage mode" = activated
The synchronization of the parameter sets is bidirectional.
The most actual data set (master or device) is valid:
The following applies:
The data set in
the device is actual, if
DS_UPLOAD_FLAG = 1
The data set in
the master is actual, if
DS_UPLOAD_FLAG = 0
Parameterizing a device in the installation:
A device, which is already used in the install
ation, is for example parameterized via a DTM.
DS_UPLOAD_FLAG = 1
o
changes in the device's para
meter see
1
IO-Link-Master
IO-Link-Device
The IO-Link device is already connected
to the master.
Para. IOLD =
parameter data of the IO-Link device
Maintenance – exchange device in delivery status:
A defective device is re
placed by a device in delivery status.
DS_UPLOAD_FLAG = 0
o
no changes in the device's parameter set
0
IO-Link-Master
IO-Link-Device
The IO-Link device has not been con-
nected to the IO-Link master
before.
Para. IOLD =
parameter data of the IO-Link device