37
V01.0| 2017/04

TBPN-L1-FDIO1-2IOL - Standard IO-Link
5.2.4 Subindex 68: Master Port Scan Configuration
28 byte are returned per IO-Link port
IO-Link
Port
Content Length Format Description
Port 1 Vendor_ID 2 byte UINT16 Vendor ID of the connected device
Device_ID 4 byte UINT32 Device-ID of the connected device
Function_ID 2 byte UINT16 reserved
Serial_Number 16 byte String Serial number of the connected device
COM_Revision 1 byte UINT8 IO-Link version
Proc_In_Length 1 byte UINT8 Process input data length of the con-
nected device
Proc_Out_Length 1 byte UINT8 Process output data length of the con-
nected device
Cycle time UINT8 Cycle time of the connected device
Port 2 Structure similar to port 1
.
Entity_
Port
IO-Link
subindex
Read
Write
Length Description
0 68 r max. 120 byte This object
serves for reading the
Configuration of the IO-Link devices con-
nected to the IO-Link master.