19
V01.00| 2017/04
TBPN-L1-FDIO1-2IOL- Safe I/O channels
3.6 Technical data
3.6.1 Safety characteristic data
3.6.2 General technical data
Characteristic data Value
Performance Level (PL) e DIN EN ISO 13849-1
Safety category 4 DIN EN ISO 13849-1
Safety Integrity Level (SIL) 3 IEC/EN 61508
SIL CL 3 according to EN/IEC 62061
PFH 4 × 10
-9
according to IEC/EN 61508
PFD 5 × 10
-5
according to IEC/EN 61508
MTTF
d
10000 years
DC 99 %
Permissible duration of use (TM) 20 years DIN EN ISO 13849-1
Maximum on-time 12 months IEC/EN 61508
Max. reaction time in case of shutdown
PROFIsafe > local output 25 ms IEC/EN 61508
Local input > PROFIsafe 20 ms
Local input <> local output 35 ms
Supply voltage
V1 (incl. electronics supply) 24 V DC
Permissible range 20,4}28,8 VDC
V2 24 VDC, not used in module, only connected through for
further use
Isolation voltages
V1 to V2 t500 V AC
V1/V2 to the field bus t500 V AC
Connectors
Ethernet 2 x M12 connector (OUT), 4-pole, D-coded
PROFIBUS 1 x M12-male (IN), 5-pole, B-coded
1 x M12-female (OUT), 5-pole, B-coded
Power supply 7/8" connector, 5-pole
In-/outputs M12 connector, 5-pole
Permissible torques
Ethernet 0.6 Nm
I/O channels/supply. 0.8 Nm
Mounting (M6 screws) 1.5 Nm
Protective cap 0.5 Nm
Protocol properties PROFINET
F_address setting via rotary coding switches
MinCycleTime 1 ms
Fast Start-Up (FSU) not supported
Diagnostics according to PROFINET Alarm Handling
Topology detection supported
Automatic address assignment supported
Media Redundancy Protocol (MRP) supported