Product description
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
16
3.4 Connection options at device
3.4.1 PROFINET
The connection to Ethernet is realized via the integrated auto-crossing switch is done using two 4-
pole, D-coded M12 x 1-Ethernet connectors.
Ethernet M12 x 1
ETH1 ETH2
v
4
1
3
2
P1
1 = TD +
2 = RD +
3 = TD –
4 = RD –
v
4
1
3
2
P2
1 = RD +
2 = TD +
3 = RD –
4 = TD –
Fig. 4: Pin assignment of M12 x 1-Ethernet connectors, 4-pole
3.4.2 Power supply
The power supply is realized via 7/8" male connectors on the module.
V1 and V2 are galvanically isolated.
Supply voltage 7/8", 5-pole
1 BK = V2 (–)
2 BU = V1 (–)
3 GNYE = FE
4 BN = V1 (+)
5 WH = V2 (+)
3
4
5
2
1
wv
3
4
5
2
1
X1 X2
X1= voltage IN
X2 = voltage OUT for supplying the next node
V1 = supply voltage 1 (incl. supply of electronics)
V2 = supply voltage 2 (not used in the device, only looped
thro
ugh)
Fig. 5: Power supply