Configuring with Turck Safety Configurator
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
58
7.12.4 Switch off of FDX4/5 if emergency shutdown or light grid activated
Output FDX4/5 at C2 (3. has to be switched off as soon as the emergency shutdown
at FDI0/1 (64. OSSD) or the light grid at FDI2/3 (63. OSSD) are activated. This means, the state of the
OSSD
63 and 64 controls the state of FDX4/5.
h Delete "Output F-CPU" in the release circuit 3 (3. OSSD).
h Select the block "State of output switching element" from the Device library and place it at the
function input. In the dialog box "State of output switching element x" select OSSD 63.
Fig. 38: State of output switching element OSSD 63