Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
8
2.5 Process data of the DXP channels
2.5.1 Process image TBPN-L1-FDIO1-2IOL
Process input data – complete module
NOTE
Further information about the parts of he process image of TBPN-L1-FDIO1-2IOL which
concern the safe I/O channels and the IO-Link channels can be found in the user manuals
Part 1 "User manual – TBPN-L1-FDIO1-2IOL – Safety" and Part 3 "User manual – TBPN-L1-
FDIO1-2IOL – IO-Link master".
The parts, which are relevant for the standard I/O channels are shown in bold.
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
n to
n + 3
Universal I/O channels
and IO-Link master channels
(page-9)
n + 4 to n
+ 23
Safe I/O channels
n + 24 to n
+ 87
IO-Link process input data
Diagnostics
(page-10)
n + 88
to
n + 89
Overcurrent diagnostics
n + 90
to
n + 91
DXP diagnostics
n + 92
to n + 95
IO-Link port diagnostics
n + 96
to
n + 159
IO-Link Events
n + 160 to
n + 161
Module status
see D301375, Status and control word (page 68)