5.2.5 Subindex 69: Extended Port Diagnostics
Structure of the Extended Port Diagnostics:
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte 0
NO_SIO TCYC - - DS_F NO_DS - -
Byte 1 - WD MD PDI_H - PDI_E NO_PD -
Byte 3
Byte 4
Device status according to IO-Link specification (see Device Status (page 39))
Diagnostic bit Meaning
NO_DS The parameterized port mode (see Parameters (page 17)) does not support data
storage.
Remedy:
Change the parameterization of the port.
DS_F Error in the data storage, synchronization not possible
Possible causes:
Connected device does not support data storage
Overflow of the data storage buffer
Remedy:
Connect a device that supports data storage.
Clear the data storage buffer.
Deactivate the data storage.
TCYC The device does not support the cycle time parameterized in the master.
Remedy:
Increase the cycle time set in the master
NO_SIO The device does not support the standard DI mode (see parameter Mode (page
17)).
Remedy:
Select the IO-Link mode for this port.
NO_PD No process data available The connected device is not ready for operation.
Remedy:
Checking the configuration
PDI_E The connected device reports invalid process data in accordance with IO-Link
specificati
on V1.0.
PDI_H The connected device reports invalid process data in accordance with IO-Link
specificati
on V1.1.
MD Missing device: No IO-Link device detected
Remedy:
Check the IO-Link cable.
Change the device.
WD Wrong device detected: one or more parameters of the connected device (Ven-
dor ID, Device ID, serial number) does not
/do not match the data which are stored
in the master for this device.
Remedy:
Change the device.
Adapt the master parameterization (see parameter Mode (page 17))
Entity_
Port
IO-Link
subindex
Read
Write
Length Description
0 69 r max. 8 byte This object serves for reading the
Extended
Port Diagnostics.