TBPN-L1-FDIO1-2IOL - Standard IO-Link
IO-Link master diagnostics
PPE Port parameterization
The port parameters are inconsistent.
The device parameterization via GSD is active, but not working.
Possible causes:
The IO-Link-master did not receive GSDML-parameters for a connected device. The con-
nected device was not parameterized by a PROFINET PLC via GSDML.
The port is in operation mode "IO-Link without validation" or "DI". These modes do not allow
parameterization via GSD.
The data storage mode is active, which means, the parameter is not set to "deactivated,
clear". A device parameterization via GSDML is not possible with activated data storage.
Vendor or Device ID are "0". The connected device can not be identified and is thus not
parameterizable.
CFGER Wrong or missing device
The connected device does not match the
channel configuration or there is no device
connected to the channel.
This diagnostic message depends on the
parameterization of the channel (see
parameters,
page 17).
Change the parameterization of the IO-Link
port at the master.
Correct the vendor-ID, device-ID, etc.
The parameterization can be done by teaching
the master via IOL_CALL using the port func-
tion
Subindex 67: Teach Mode or via a
manual port parameterization.
DSER Data storage error
Possible causes:
– Data storage mismatch IO-Link device in accordance with IO-Link V1.0
connected.
Deactivate the data storage.
To do so, set parameter
"
Data storage mode" to "deactivated,
clear", see
page 19.
The data storage buffer contains data of
another device.
Clear the data storage buffer of the master.
To do so, set the parameter "
Data storage
mode
" to "deactivated, clear", see , and re-
activate the data storage if necessary.
– Overflow of the data storage buffer Clear the data storage buffer of the master.
To do so, set the parameter "
Data storage
mode
" to "deactivated, clear", see page 19,
and re-activate the data storage if necessary.
– Parameter access for data storage not
possible
The connected device may be locked for
parameter changes or for data storage.
Check the status of the IO-Link index "Device
Access Locks" (index 0xC) of the connected
device and unlock the device.
Bit Meaning Remedy