TBPN-L1-FDIO1-2IOL - Standard IO-Link
Start-up steps (2nd possibility)
Fig. 12: Activate data storage via DTM
h Set the "data storage mode" to "deactivated,
clear".
h Download the parameters int
o the device.
h Re-activate the data storage if required.
h Download the parameters int
o the device.
h Connect the IO-Link V1.1 device.
¬ LED "IOL" = GREEN (for the respective port), IO-
Link communication is active.