Chapter 3 ________________________________________________________________  Installation 
 
VAISALA ________________________________________________________________________ 55 
The following numbers refer to Figure 28 on page 54: 
T5A AC Heater line fuse for PWD32 
T5A AC Heater line fuse for LM21 
M10A AC Heater line fuse for FSM102 
Power switch and circuit breaker 
AC (mains) surge supressor 
 
NOTE 
If the line voltage used differs from 230
 V (the initial factory setting), 
check the voltage setting of the FSP103 
AC (mains) power supply 
 VAC and 230 VAC). See Figure 28 on page 54. 
 
Communication Cable 
The enclosure of the interface unit FSI102 has a data cable outlet for 
cable diameters of 8 to 11 mm. This is reserved for signal or modem 
cables. The optional AC (mains)/data cable outlet can also be used for 
data cables. The cable should be led out from the unit inside the lower 
mast section. Grounding must be done within the cable gland in order to 
keep the EMI levels within specifications. 
NOTE 
on box installed, the cable shield should be grounded 
at both the input and output cable glands.
 
 
Detailed instructions for a proper RF grounding of any jacketed cables 
are given in the following: 
1.  Lead the signal cable through the cable inlet. See Figure 29 on page 
56. 
2.  Strip 50 cm of the cable sheath leaving approximately 2 cm of 
shield.