EasyManua.ls Logo

Vaisala HMT370EX - UK (UKEX) Safety Certification Information

Vaisala HMT370EX
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Equipment part Allowed ambient temperature range
Probe head HMP371 Temperature class T4:
-40 °C … +60 °C (-40 … +140 °F)
Probe head HMP373 Rubber cable version:
Temperature class T6:
-40 °C … +55 °C (-40 … +131 °F)
Temperature class T5:
-40 °C … +80 °C (-40 … +176 °F)
FEP cable version:
Temperature class T6:
-40 °C … +55 °C (-40 … +131 °F)
Temperature class T5:
-40 °C … +100 °C (-40 … +212 °F)
Temperature class T4:
-40 °C … +120 °C (-40 … +248 °F)
Probe heads HMP374, HMP375, HMP377,
HMP378, HMP378F, and HMP378H
Temperature class T6:
-70 °C … +55 °C (-94 … +131 °F)
Temperature class T5:
-70 °C … +100 °C (-94 … +212 °F)
Temperature class T4:
-70 °C … +135 °C (-94 … +275 °F)
Temperature class T3:
-70 °C … +180 °C (-94 … +356 °F)
3.7.2.1 Specific conditions of use
With the installation of the equipment in Zone 0 Group II area it has
to be ensured that sparks due to impact or friction do not occur.
CAUTION!
Wiring requirements
Only use cables and cable glands suitable for +80 °C (+176 °F)
The cable glands and cables used for wiring the device must not impair the Ex protection.
Unused lead-throughs must be sealed using Ex compliant plugs.
Select a strain relief option that suits the application (either use cable glands that include
strain relief or install separate clamps: see IEC 60079-14).
Chapter 3 – HMT370EX regional safety certification information
53

Table of Contents

Related product manuals